2355 Wood Dale Road, Elk Grove, Illinois
Up to 115,000 square feet. Available for Lease Delivery June, 2001
Innovative
Engineering & Pre-Installed Infrastructure
Locator Map
Innovative
Engineering & Pre-Installed Infrastructure
- Newly constructed,
fortified concrete and steel construction containing a total of
115,000 square feet (100,000 square feet on the first floor and
15,000 square feet on the second floor) designed to accommodate
a maximum of 3,750 racks
- Secured Mechanical
Yard containing 18,000 square feet
- Limited glass
line offers aesthetic appeal without compromising securitythere
are no external window penetrations in the mission critical areas
- Independent
dual grid electrical service (9 MVA/12.47 k V/3 phase) enabling
100 watts/square feet... scalable to 18 MVA/12.47k V/3 phase
- Pre-installation
four (4) 12.47kV/480v substations with 4,000 amp/480v/3
phase distribution boards with Transient Voltage Surge Suppressors
- Pre-Installation
of three (3) 2,000 kW Caterpillar Generators scalable to nine
(9) 2,000 kW generators
- Pre-installation
of Paralleling Switchgear capable of modular expandability to
accommodate nine (9) 2,000 kW generators (the capacity necessary
for N+1 redundancy for the entire facility)
- 25
clear ceiling heights throughout (11 in Mezzanine) with
48 x 397" bays
- Design provisions
for triple overhead racks (100lbs/LF)
- Industrial
strength slab at grade (350 lbs live load/SF)
- Concrete
roof deck free of internal drains
- Fully adhered
GAF roof system (twenty year warranty) rated to withstand 150
mph wind
- Dual Points
of Entry for telecommunications access with twelve 4-inch conduits
at each point of entry
- Diversity
of telecom providers at site: Qwest Node, Level3 and Ameritech
- "Room
Ready" Demarcation Area for telecommunications pre-installation
- Installation
of Tenants preferred cooling system
- Pre-installation
of Equi potential ground grid
- Pre-action
sprinkler valves with design provisions for high sensitivity smoke
detection
- Perimeter
security fencing with controlled access to parking and mechanical
yard
- Design provisions
for CCTV monitoring
- Active and
passive lightning protection systems
- Pre-installation
of rough-in for ADA compliant restrooms
Additionally,
DataCentersNowSM has taken possession of
Sixty (60) 30-ton Air-cooled Liebert DX units and 50,000 sq. ft.
of Tate raised flooring for the immediate installation at the site
per your design criteria.
* Specifications
subject to change without notice.
|