2355 Wood Dale Road, Elk Grove, Illinois
Up to 115,000 square feet. Available for Lease Delivery June, 2001

Innovative Engineering & Pre-Installed Infrastructure
Locator Map

Innovative Engineering & Pre-Installed Infrastructure

  • Newly constructed, fortified concrete and steel construction containing a total of 115,000 square feet (100,000 square feet on the first floor and 15,000 square feet on the second floor) designed to accommodate a maximum of 3,750 racks
  • Secured Mechanical Yard containing 18,000 square feet
  • Limited glass line offers aesthetic appeal without compromising security—there are no external window penetrations in the mission critical areas
  • Independent dual grid electrical service (9 MVA/12.47 k V/3 phase) enabling 100 watts/square feet... scalable to 18 MVA/12.47k V/3 phase
  • Pre-installation four (4) – 12.47kV/480v substations with 4,000 amp/480v/3 phase distribution boards with Transient Voltage Surge Suppressors
  • Pre-Installation of three (3) 2,000 kW Caterpillar Generators scalable to nine (9) 2,000 kW generators
  • Pre-installation of Paralleling Switchgear capable of modular expandability to accommodate nine (9) 2,000 kW generators (the capacity necessary for N+1 redundancy for the entire facility)
  • 25’ clear ceiling heights throughout (11’ in Mezzanine) with 48’ x 39’7" bays
  • Design provisions for triple overhead racks (100lbs/LF)
  • Industrial strength slab at grade (350 lbs live load/SF)
  • Concrete roof deck free of internal drains
  • Fully adhered GAF roof system (twenty year warranty) rated to withstand 150 mph wind
  • Dual Points of Entry for telecommunications access with twelve 4-inch conduits at each point of entry
  • Diversity of telecom providers at site: Qwest Node, Level3 and Ameritech
  • "Room Ready" Demarcation Area for telecommunications pre-installation
  • Installation of Tenant’s preferred cooling system
  • Pre-installation of Equi potential ground grid
  • Pre-action sprinkler valves with design provisions for high sensitivity smoke detection
  • Perimeter security fencing with controlled access to parking and mechanical yard
  • Design provisions for CCTV monitoring
  • Active and passive lightning protection systems
  • Pre-installation of rough-in for ADA compliant restrooms

Additionally, DataCentersNowSM has taken possession of Sixty (60) 30-ton Air-cooled Liebert DX units and 50,000 sq. ft. of Tate raised flooring for the immediate installation at the site per your design criteria.